Short Circuit Capacity MCQ Quiz - Objective Question with Answer for Short Circuit Capacity - Download Free PDF
Last updated on May 14, 2025
Latest Short Circuit Capacity MCQ Objective Questions
Short Circuit Capacity Question 1:
In a ring distribution system, if one section of the ring experiences a fault and is disconnected, how does this affect the voltage drop at the loads connected to the remaining operational sections?
Answer (Detailed Solution Below)
Short Circuit Capacity Question 1 Detailed Solution
Ring distribution system
- A ring distribution system is an electrical power distribution network where feeders connect in a closed loop, providing multiple paths for power delivery.
- This design ensures that if one feeder fails, power can continue to flow through an alternative path, maintaining reliability and preventing power outages.
- There are fewer voltage fluctuations at the consumer's terminal.
Short Circuit Capacity Question 2:
With reference to line protection, state True/False for the following statements:
1. In the event of a short circuit, the circuit breaker closest to the fault should open.
2. The relay operating time should be as large as possible.
Answer (Detailed Solution Below)
Short Circuit Capacity Question 2 Detailed Solution
Circuit breaker
- A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by current more than that which the equipment can safely carry (overcurrent).
- Its basic function is to interrupt current flow to protect equipment and to prevent fire.
- In power systems, protection schemes follow the principle of selective coordination. The circuit breaker closest to the fault (downstream) must trip first to isolate the fault while keeping the rest of the system operational.
- This prevents unnecessary disconnection of large portions of the electrical network.
Statement 1 is True.
Relay
- Relays are electrically operated switches that open and close the circuits by receiving electrical signals from outside sources.
- Relays should operate as quickly as possible to minimize damage to equipment and ensure safety.
Statement 2 is False.
Short Circuit Capacity Question 3:
State True/False for the following statements with reference to commutation of SCRs:
1. Class D commutation is a complementary commutation.
2. Class F commutation is a natural commutation.
Answer (Detailed Solution Below)
Short Circuit Capacity Question 3 Detailed Solution
Commutation
Commutation refers to the process of turning off a conducting thyristor. There are six major types of commutation methods, classified into two categories:
Category 1: Forced Commutation
- It is used in DC circuits where the current does not naturally reach zero. It requires external components (capacitors, inductors) to force the current to zero.
- Forced commutation is classified into five commutation techniques.
Class A (Resonant Commutation)
- Uses an LC circuit to create oscillations that naturally bring the current to zero, turning off the thyristor.
- Completely independent of external circuit components.
Class B (Resonant-Pulse Commutation)
- The thyristor is turned off using an LC resonant circuit discharging when the current reaches zero.
Both Class A and Class B rely on the circuit's natural behavior to turn off the thyristor, making them self-commutation methods.
Class C: Complementary Commutation
- Uses another thyristor (auxiliary SCR) and a capacitor to turn off the main thyristor.
- Used in DC choppers and inverters.
Class D: Auxiliary Commutation
- Similar to Class C but uses an external voltage source to force commutation. Used in high-power inverters and choppers.
Class E: External Pulse Commutation
- Uses an external commutation pulse from a circuit to turn off the thyristor.
- Used in Cycloconverters and high-power circuits.
Category 2: Class F (Natural Commutation)
- It occurs in AC circuits where the current naturally becomes zero. In AC applications, the supply voltage reverses polarity every half-cycle, automatically bringing the current to zero.
- Example: Line commutation in rectifiers.
Short Circuit Capacity Question 4:
State True/False for the following statements, with reference to overload and short circuit in power systems:
1. The voltage at the overload point may be low, but not zero.
2. The currents in the overloaded equipment are substantially lower than that in the case of a short-circuit.
Answer (Detailed Solution Below)
Short Circuit Capacity Question 4 Detailed Solution
Overload in Power System
- An overload occurs when electrical equipment or a circuit carries more current than its rated capacity, but there is no direct fault or connection between phases or ground.
- This condition can cause the wiring to overheat, potentially leading to a fire. Common signs include tripped circuit breakers, flickering lights, and unusual buzzing or sizzling sounds from electrical outlets.
- In an overload condition, the electrical load exceeds the rated capacity, causing a voltage drop but not a complete loss of voltage. Unlike a short circuit, where voltage at the fault point is nearly zero, an overload only reduces the voltage.
Hence, Statement 1 is True.
Short Circuit in the Power System
- A short circuit is an unintentional, low-resistance connection between two points in a circuit, allowing excessive current to flow, bypassing the intended load path. This can be caused by damaged insulation, faulty wiring, or accidental contact, leading to potential hazards like overheating, fires, and equipment damage.
- In an overload, the current is higher than normal but still within a limited range (e.g., 2-5 times the rated current).
- In a short circuit, the current can be hundreds or thousands of times the normal current, depending on system impedance.
- Therefore, overload current is substantially lower compared to short-circuit current.
Hence, Statement 2 is True.
Short Circuit Capacity Question 5:
Connecting a lead from the negative to the positive of a battery will produce
Answer (Detailed Solution Below)
Short Circuit Capacity Question 5 Detailed Solution
Explanation:
Connecting a lead from the negative to the positive of a battery creates a direct connection between the two terminals of the battery without any significant resistance or load in between.
This condition is known as a short circuit.
In a short circuit, the current flow is very high because the resistance of the connection is very low. This can lead to overheating and potential damage to the battery and the circuit.
Therefore, the correct answer is:
Option 2: a short circuit
Top Short Circuit Capacity MCQ Objective Questions
A transformer is rated at 11 kV/0.4 kV, 500 KVA, 5% reactance. What is the short circuit MVA of the transformer when connected to an infinite bus?
Answer (Detailed Solution Below)
Short Circuit Capacity Question 6 Detailed Solution
Download Solution PDFConcept:
Short circuit MVA = \( \frac{{\;\ MVA}_{base}}{{{X_{pu}}}}\)
Where,
MVAbase = Full load or base MVA
Xpu = Per unit reactance
Calculation:
Given that, MVAbase = 500 kVA = 0.5 MVA, Xpu= 5% = 0.05
Since the transformer is connected to an infinite bus, the p.u. the reactance of the circuit will be 0.05 i.e., the p.u. reactance offered by the transformer.
∴ short circuit MVA can be calculated as
Short circuit MVA = \( \frac{{\ 0.5}}{{{0.05}}} =10 ~MVA\)
If the percentage reactance of an element is 20% and the full load current is 40 A, then short circuit current will be __________, when only that element is in the circuit.
Answer (Detailed Solution Below)
Short Circuit Capacity Question 7 Detailed Solution
Download Solution PDFThe correct answer is option 2): (200 A )
Concept:
The short circuit current is given by
Isc = I × \(100 \over percentage\: of \: reactance\)
Where
I is the full load current
Calculation:
Isc = I × \(100 \over percentage\: of \: reactance\)
= 40 × \(100 \over 20\)
= 200 A
A 50 Hz, 4 Pole, 500 MVA, 22 kV turbo generator is delivering rated MVA at a power factor of 0.8. Suddenly a fault occurs reducing the electric power output by 40%. Neglect the losses and assume constant power input to the shaft. The accelerating torque in the generator at the time of fault is
Answer (Detailed Solution Below)
Short Circuit Capacity Question 8 Detailed Solution
Download Solution PDFConcept:
Accelerating power can be calculated as
Pa = Pm – Pe
Accelerating torque is given as
\({T_a} = \frac{{{P_a}}}{{{\omega _s}\;}}\)
Where,
Pm = Mechanical input power
Pe = Electrical output power
ωs = Synchronous speed in radian/sec
P = Number of poles
F = Supply frequency
Synchronous speed in rpm can be calculated as
\({N_s} = \frac{{120f}}{P}\)
Also, \({\omega _s} = \frac{{2\pi {N_s}}}{{60}}\)
Calculation:
Given-
f = 50 Hz, P = 4
Before fault
Pm = Pe = 500 cosϕ = 500 x 0.8
Pm = Pe = 400 MW
After fault Pm remains same, while Pe reduces by 40%
So electrical output at the time of fault is
Pe’ = (1 – 0.4) = 0.6 x 400
Pe’= 240 MW
Now Accelerating power at the time of fault is
Pa’ = 400 – 240 = 160 MW
Now synchronous speed is
\({N_s} = \frac{{120 \times 50}}{4} = 1500\;rpm\)
\({\omega _s} = \frac{{2\pi \times 1500}}{{60}} = 157\;radian/sec\)
Hence accelerating torque is
\({T_a} = \frac{{160 \times {{10}^6}}}{{157}} = 1.018\; \times {10^6}\;N - m\)
Ta = 1.018 MN-m
Five alternators, each of which is rated for 10 MVA, 11 KV with 25% reactance, operate in parallel order. What will be the short circuit level in the bus bar?
Answer (Detailed Solution Below)
Short Circuit Capacity Question 9 Detailed Solution
Download Solution PDFConcept:
Short circuit MVA or Fault MVA = (Base MVA) x 100 / (% X)
Where,
X = Thevenin equivalent reactance between fault point and zero power bus (ZPB)
Calculation:
Base MVA = 10 MVA
According to the given data, the circuit diagram & per unit diagram can be drawn as given below.
Line diagram:
Per unit diagram:
Thevenin equivalent circuit:
\(X = \frac{{0.25}}{5} = 0.05\;{\rm{\Omega }}\)
% X = 5 %
Now short circuit MVA can be calculated as
Short circuit MVA or Fault MVA = (10)/0.05
Short circuit MVA or Fault MVA = 200 MVA
______ is defined as maximum current can flow through the breaker from time of occurring short circuit to the time of clearing the short circuit without any permanent damage in the Circuit breaker.
Answer (Detailed Solution Below)
Short Circuit Capacity Question 10 Detailed Solution
Download Solution PDFThe correct answer is option 2):(short circuit breaking current)
Concept:
- The short circuit breaking current is defined as the maximum current that can flow through the breaker from the time occurring short circuit to the time of clearing the short circuit without any permanent damage to the Circuit breaker
- The rated short-circuit-breaking-current of a circuit-breaker is the highest value of short circuit current which a circuit-breaker is capable of breaking under specified conditions of transient recovery voltage and power frequency voltage. It is expressed in kA r.m.s. at contact separation.
Additional Information
- The rated short-circuit-making current is the maximum peak current that the switch shall be capable of making at its rated voltage.
- The rated normal current of a circuit breaker is the r.m.s. value of the current which the circuit breaker can carry continuously and with temperature rise of the various parts within specified limits
Five alternators each rated 5 MVA, 13.2 kV with 25% of reactance on its own base are connected in parallel to a busbar. The short-circuit level in MVA at the busbar is_________.
Answer (Detailed Solution Below) 100
Short Circuit Capacity Question 11 Detailed Solution
Download Solution PDFReactance of each alternator = 0.25
As all the five alternators are connected in parallel, the equivalent reactance
\({X_{eq}} = \frac{{0.25}}{5} = 0.05\;pu\)
short circuit \(MVA = Base\frac{{MVA}}{{{X_{eq}}}} = \frac{5}{{0.05}} = 100\;MVA\)______ can be defined as an abnormal connection of very low impedance between two points of different potential, whether made intentionally or accidentally.
Answer (Detailed Solution Below)
Short Circuit Capacity Question 12 Detailed Solution
Download Solution PDFThe correct answer is option 2):(Short circuit faults)
Concept:
- A short circuit can be defined as an abnormal connection of very low impedance between two points of different potential, whether made intentionally or accidentally.
- These are the most common and severe kinds of faults, resulting in the flow of abnormally high currents through the equipment or transmission lines
- These faults can be caused by a lightning strike, weather conditions or equipment failure. During the fault, the system can see a direct connection to the earth and current flows from all sources into it.
Additional Information
- An unsymmetrical or asymmetrical fault is defined as a fault that affects one or two phases of a three-phase system in contrast with the previously studied balanced or symmetrical faults which equally affect each of the three phases
- A symmetrical fault is a fault where all phases are affected so that the system remains balanced
- An open-circuit fault occurs if a circuit is interrupted by a failure of a current-carrying wire (phase or neutral) or a blown fuse or circuit breaker.
Five identical alternators rated at 11 kV, 25 MVA are connected in parallel. Find the short circuit MVA at the terminal, if the sub transient reactance of each alternator is 20%.
Answer (Detailed Solution Below)
Short Circuit Capacity Question 13 Detailed Solution
Download Solution PDFThe correct answer is option 2): (625)
Concept:
Short-circuit MVA is a measure of the electrical strength of the bus. It determines the dimension of the bus bar and the interrupting capacity of a circuit breaker. The short circuit MVA of each component is defined as the ratio of MVA rating to its own per unit reactance.
It is also called a Fault MVA.
Short circuit = \(\frac{Base MVA }{Reactance}\)
Calculation:
Short Circuit MVA = \(\frac {Number of alternators×MVA ~rating }{ Sub-transient reactance (in per unit)}\)
Given
No of alternators = 5
Base MVA = 25 MVA
Rated Voltage = 11 KV
Sub transient reactance of each alternator = 20 %= 0.2 per unit
X = \(\frac{0.2}{5}\) = 0.04 per unit (as 5 alternator connected in parallel)
Short circuit = \(\frac{Base MVA }{Reactance}\)
= \(\frac{25}{0.04}\)= 625 MVA
Two parallel alternators each rated 11 kV 50 MVA and each having sub transient reactance of 15% are connected to a bus bar. What is the fault level for a fault on one of the feeders near the bus bar?
Answer (Detailed Solution Below)
Short Circuit Capacity Question 14 Detailed Solution
Download Solution PDFShort Circuit Capacity:
- It is the measure of the electrical strength of the bus
- It is also called short-circuit MVA stated in MVA.
- It determines the dimension of the bus bar and the interrupting capacity of a circuit breaker.
Finding the fault level:
\({I_{SC}} = \frac{{{V_b}}}{Z} = \frac{{{V_b}/{Z_b}}}{{Z/{Z_b}}} = \frac{{{I_b}}}{{{Z_{p.u.}}}}\)
Where,
ISC is the short circuit current
Vb is the base voltage
Z impedance of the alternator
Zb is the base impedance of the alternator
Zp.u. per unit impedance of the alternator
\(\sqrt 3 {V_b}{I_{SC}} = \frac{{\sqrt 3 {V_b}{I_b}}}{{{Z_{p.u.}}}}\)
\(MV{A_{SC}} = \frac{{MV{A_b}}}{{{Z_{p.u.}}}}\)
The percent value is the per-unit value multiplied by 100 (Z% = Zp.u. × 100)
Calculation:
Given,
MVAb = 50 MVA
As the alternators having only reactance (Zp.u. = Xp.u.)
Zp.u. = 15 / 100
= 0.15
As the alternators are connected in parallel
Xp.u. = 0.15 / 2
= 0.075
The fault level for a fault on one of the feeders near the bus bar
MVASC = 50 / 0.075
= 666.67 MVA
Therefore, the fault level for a fault on one of the feeders near the bus bar is 666.67 MVA
Two generator units G1 and G2 are connected by 15kV line with a bus at the mid-point as shown below
G1 = 250 MVA, 15 kV, positive sequence reactance XG1 = 25% on its own base
G2 = 100 MVA, 15 kV, positive sequence reactance XG2 = 10% on its own base L1 and L2 = 10 km, positive sequence reactance XL = 0.225 Ω/km
In the above system, the three – phase fault MVA at the bus 3 is
Answer (Detailed Solution Below)
Short Circuit Capacity Question 15 Detailed Solution
Download Solution PDF\(\begin{array}{l} {X_{{G_1}}} = 0.25 \times \frac{{100}}{{250}}{\left( {\frac{{15}}{{15}}} \right)^2} = 0.1\\ {X_{{G_2}}} = 0.1 \times \frac{{100}}{{100}}{\left( {\frac{{15}}{{15}}} \right)^2} = 0.1\\ {X_{{L_1}}} = 0.225 \times 10 \times \frac{{100}}{{{{\left( {15} \right)}^2}}} = j1.0\\ {X_{{L_2}}} = 0.225 \times 10 \times \frac{{100}}{{{{\left( {15} \right)}^2}}} = j1.0 \end{array}\)
Reactance diagram:
We can see that at bus 3, equivalent Thevenin's impedance is given by
Xth = (j 0.1 + j 1.0)||(j 0.1 + j 1.0) = j .55 pu
Fault MVA = (Base MVA / Xth) = 100 / .55 = 181.82 MVA