Line To Line To Line Fault MCQ Quiz - Objective Question with Answer for Line To Line To Line Fault - Download Free PDF
Last updated on Jun 11, 2025
Latest Line To Line To Line Fault MCQ Objective Questions
Line To Line To Line Fault Question 1:
For a fault at terminals of the synchronous generator, the fault current is maximum for a:
Answer (Detailed Solution Below)
Line To Line To Line Fault Question 1 Detailed Solution
Explanation:
Fault Current in Synchronous Generators:
Definition: When a fault occurs at the terminals of a synchronous generator, the generator's response to the fault depends on the type of fault. Fault current is the current that flows during a fault condition, which is significantly higher than the normal operating current. The magnitude of the fault current depends on the type of fault and the impedance of the system.
Correct Option Analysis:
The correct option is:
Option 1: Three-phase fault.
Among all types of faults that can occur in a power system, a three-phase fault generates the highest fault current. This is because a three-phase fault involves all three phases of the system, creating a condition where the impedance of the fault path is minimum. As a result, the current during a three-phase fault is maximum compared to other types of faults.
Why Three-Phase Fault Produces Maximum Fault Current:
- Symmetrical Nature: A three-phase fault is a balanced fault, meaning all three phases are equally affected. This symmetry ensures that the fault current magnitude is uniform across all three phases, leading to the highest possible current flow.
- Minimum Fault Impedance: During a three-phase fault, the impedance of the fault path is at its lowest, as all three phases are directly short-circuited. Lower impedance results in higher current flow as per Ohm's Law (I = V/Z, where I is current, V is voltage, and Z is impedance).
- Generator's Response: Synchronous generators are designed to supply balanced three-phase power. When a three-phase fault occurs, the generator supplies maximum current to the fault because the fault aligns with the generator's natural three-phase configuration.
Implications of Three-Phase Fault:
- It is the most severe type of fault in terms of current magnitude and system impact.
- Protection systems, such as circuit breakers and relays, are designed to detect and isolate three-phase faults quickly to prevent damage to equipment and ensure safety.
- System studies and fault analysis prioritize three-phase fault scenarios to design robust protection schemes and ensure system stability.
Additional Information
To further understand the analysis, let’s evaluate the other options:
Option 2: Double line to ground fault.
A double line to ground fault involves two phases and the ground. While this type of fault results in a higher fault current than single line to ground or line-to-line faults, it does not exceed the fault current produced by a three-phase fault. The presence of ground in the fault path increases impedance compared to a three-phase fault, reducing the current magnitude.
Option 3: Line to line fault.
A line-to-line fault involves a short circuit between two phases. The fault current in this scenario is lower than that of a three-phase fault because only two phases are involved, and the impedance in the fault path is higher. Line-to-line faults are less severe than three-phase faults in terms of current magnitude and system impact.
Option 4: Line to ground fault.
A line-to-ground fault occurs when one phase is short-circuited to the ground. This type of fault has the highest impedance among all fault types, resulting in the lowest fault current. While line-to-ground faults are common in power systems, their impact is less severe compared to other faults.
Conclusion:
Among all types of faults, a three-phase fault produces the maximum fault current due to its symmetrical nature and minimum fault impedance. This makes it the most severe fault type in terms of system impact, requiring robust protection systems to mitigate its effects. Understanding the characteristics of different fault types is essential for designing effective power system protection schemes and ensuring system stability.
Line To Line To Line Fault Question 2:
Which of the following faults is least likely to occur in power systems?
Answer (Detailed Solution Below)
Line To Line To Line Fault Question 2 Detailed Solution
Among the given faults, LLLG or 3 phase fault is the most severe and least likely to occur in the power system. LG or line to ground fault is most common and occurs frequently.
Symmetrical Fault:
The faults which involve all three phases are known as the symmetrical fault. Such types of faults remain balanced even after the fault. The symmetrical faults mainly occur at the terminal of the generators.
- The three-phase line to the ground fault (LLLG): The three-phase line to ground fault includes all the three-phase of the system. The LLLG fault occurs between the three phases and the ground of the system. The probability of occurrence of such type of fault is nearly 2 to 3 percent.
Unsymmetrical Fault:
The fault gives rise to unsymmetrical current, i.e., current differing in magnitude and phases in the three phases of the power system are known as the unsymmetrical fault. It is also defined as the fault which involves one or two phases such as LG, LL, LLG fault. The unsymmetrical makes the system unbalanced.
- Single Line to Line Ground (SLG): The single line of ground fault occurs when one conductor falls to the ground or contact the neutral conductor. The 70 – 80 percent of the fault in the power system is the single line-to-ground fault.
- Line to Line Fault (LL): A line-to-line fault occurs when two conductors are short-circuited. The major cause of this type of fault is the heavy wind. The heavy wind swinging the line conductors which may touch together and hence cause short-circuit. The percentage of such types of faults is approximately 15 – 20%.
- Double Line to line Ground Fault (LLG): In double line-to-ground fault, the two lines come in contact with each other along with the ground. The probability of such types of faults is nearly 10 %.
Frequency of occurrence:
- Among the given faults, LG or line to ground fault is most common and occurs frequently.
- The order of frequency of occurrence is given below.
LG > LL > LLG > LLLG
Severity of faults:
- Among the given faults, LLLG or 3 phase faults are most severe. LG or line to ground fault is least severe.
- Line to line fault is more severe than line to ground fault while double line to ground fault is one level severe than LL.
- The order of frequency of occurrence is given below.
LLLG > LLG > LL > LG
Conclusion: Among the given faults, LLLG or 3 phase fault is the most severe and least likely to occur in the power system. LG or line to ground fault is most common one and least severe. The line to line fault is more severe than the line to ground fault while the double line to ground fault is one level severe than LL.
Line To Line To Line Fault Question 3:
A generator is connected to a synchronous motor through a transformer. Reduced to the same base, the pu sub transient reactance’s of the generator and motor are 0.15 pu and 0.35 pu respectively, the leakage reactance of the transformer being 0.1 pu. 3 phase fault occurs at terminals of the motor when the terminal voltage of the generator is 0.9 pu and the output current of the generator is 1 pu at 0.8 pf lag load. Sub transient current fed by the generator in pu is ______
Answer (Detailed Solution Below) 3.7 - 4.2
Line To Line To Line Fault Question 3 Detailed Solution
The terminal voltage of the generator = 0.9 pu
I = 1.0 pu, p.f = 0.8 lag
Equivalent diagram can be drawn as
I = 1.0∠-cos-1 (0.8) = 1.0∠-36.86° = 0.8 - j0.6
Apply KVL,
\( {E_g^{"}} =V_t+ jI_LX_d^{''}\)
EIIg = 0.9 + 0.15 ∠90 × 1.0 ∠-36.86°
= 0.9 + (0.8 + j0.6) × ( j0.15 )
= 0.99 + j0.12
EIIg = (0.99 + j0.12) pu
\({I_g^{"}} = \frac{{{E_g}}}{{j0.15 + j0.1}}\)
\( = \frac{{0.99 + j0.12}}{{j0.25}}\)
= (0.48 - j3.96) pu
Sub-transient current in the generator due to fault is: IIIg = 3.9889 pu
Line To Line To Line Fault Question 4:
In a large interconnected power system, consider 3 buses having short circuit capacities: 1600 MVA(1) 1200 MVA(2) and 1000 MVA(3) respectively, the voltages of all the buses are 1 pu. If a 3-phase fault takes place on bus 2, the change in bus voltage is described as
Answer (Detailed Solution Below)
Line To Line To Line Fault Question 4 Detailed Solution
When a 3-phase short circuit fault occurs on bus-2, its voltage directly falls to zero i.e., ΔV2 is largest.
Whereas for bus-1 and bus-2, their respective voltages sag due to fault on bus-2.
The more is the short circuit capability of a bus, the less would be the per unit equivalent impedance between the bus and the ground.
Therefore, more will be the strength of the bus i.e., due to fault on other bus, the sag in voltage of a bus would be less, if it has larger/greater short circuit capability.
The correct relation is: ΔV2 > ΔV3 > ΔV1Line To Line To Line Fault Question 5:
The magnitude of three-phase fault currents at buses A and B of a power system are \(10\;pu\) and \(8\;pu\), respectively. Neglect all resistances in the system and consider the pre-fault system to be unloaded. The pre-fault voltage at all buses in the system \(1.0\;pu\) is . The voltage magnitude at bus B during a three-phase fault at bus A is \(0.8\;pu\). The voltage magnitude at bus A during a three-phase fault at bus B, in \(pu\), is ________.
Answer (Detailed Solution Below) 0.83 - 0.85
Line To Line To Line Fault Question 5 Detailed Solution
Voltage at bus B after 3 – phase fault at A \(= 0.8\;p.u.\)
\(\begin{array}{l} {V_B}\; = \;V\left( {prefault} \right)\;-\;{Z_{12}}\; \times \;{I_{f\left( B \right)}}\\ 0.8\; = \;1.0\;-\;{Z_{12}}\; \times \;10\\ {Z_{12}}\; = \;0.02\;p.u.\\ {V_A}\; = \;1.0\;-\;\left( {0.02\; \times \;8} \right)\\ {V_A}\; = \;0.84\;p.u \end{array}\)
Note:
For the voltage magnitude at bus B during a three-phase fault at bus A. So we use fault current of bus A
For the voltage magnitude at bus A during a three-phase fault at bus B. So we use fault current of bus B
Top Line To Line To Line Fault MCQ Objective Questions
A sustained three phase fault occurs in the power system shown in the figure. The current and voltage phasors during the fault (on a common reference), after the natural transients have died down, are also shown. Where is the fault located?
Answer (Detailed Solution Below)
Line To Line To Line Fault Question 6 Detailed Solution
Download Solution PDFConcept :
As shown in the phasor diagram
- Current I2 & I4 have phase difference of 180°. So that they cancel out each other.
- Magnitude of the current I1 is more than current I3. Also I1 is more lagging than I3
- So that fault is located at point Q.
A \(50\;MVA,\;10\;kV,\;50\;Hz\), star-connected, unloaded three-phase alternator has a synchronous reactance of 1 p.u. and a sub-transient reactance of \(0.2\;p.u.\) If a 3-phase short circuit occurs close to the generator terminals, the ratio of initial and final values of the sinusoidal component of the short circuit current is ________.
Answer (Detailed Solution Below) 4.9 - 5.1
Line To Line To Line Fault Question 7 Detailed Solution
Download Solution PDFFault current is inversely proportional to reactance during fault.
\(\Rightarrow I_f\propto\frac{1}{X}\)
\(\Rightarrow \frac{{intial\;current}}{{final\;current}} = \frac{{Synchronous\;reactance}}{{Sub - transient\;reactance}} = \frac{1}{{0.2}}\) \(= 5\)
The magnitude of three-phase fault currents at buses A and B of a power system are \(10\;pu\) and \(8\;pu\), respectively. Neglect all resistances in the system and consider the pre-fault system to be unloaded. The pre-fault voltage at all buses in the system \(1.0\;pu\) is . The voltage magnitude at bus B during a three-phase fault at bus A is \(0.8\;pu\). The voltage magnitude at bus A during a three-phase fault at bus B, in \(pu\), is ________.
Answer (Detailed Solution Below) 0.83 - 0.85
Line To Line To Line Fault Question 8 Detailed Solution
Download Solution PDFVoltage at bus B after 3 – phase fault at A \(= 0.8\;p.u.\)
\(\begin{array}{l} {V_B}\; = \;V\left( {prefault} \right)\;-\;{Z_{12}}\; \times \;{I_{f\left( B \right)}}\\ 0.8\; = \;1.0\;-\;{Z_{12}}\; \times \;10\\ {Z_{12}}\; = \;0.02\;p.u.\\ {V_A}\; = \;1.0\;-\;\left( {0.02\; \times \;8} \right)\\ {V_A}\; = \;0.84\;p.u \end{array}\)
Note:
For the voltage magnitude at bus B during a three-phase fault at bus A. So we use fault current of bus A
For the voltage magnitude at bus A during a three-phase fault at bus B. So we use fault current of bus B
Which of the following faults is least likely to occur in power systems?
Answer (Detailed Solution Below)
Line To Line To Line Fault Question 9 Detailed Solution
Download Solution PDFAmong the given faults, LLLG or 3 phase fault is the most severe and least likely to occur in the power system. LG or line to ground fault is most common and occurs frequently.
Symmetrical Fault:
The faults which involve all three phases are known as the symmetrical fault. Such types of faults remain balanced even after the fault. The symmetrical faults mainly occur at the terminal of the generators.
- The three-phase line to the ground fault (LLLG): The three-phase line to ground fault includes all the three-phase of the system. The LLLG fault occurs between the three phases and the ground of the system. The probability of occurrence of such type of fault is nearly 2 to 3 percent.
Unsymmetrical Fault:
The fault gives rise to unsymmetrical current, i.e., current differing in magnitude and phases in the three phases of the power system are known as the unsymmetrical fault. It is also defined as the fault which involves one or two phases such as LG, LL, LLG fault. The unsymmetrical makes the system unbalanced.
- Single Line to Line Ground (SLG): The single line of ground fault occurs when one conductor falls to the ground or contact the neutral conductor. The 70 – 80 percent of the fault in the power system is the single line-to-ground fault.
- Line to Line Fault (LL): A line-to-line fault occurs when two conductors are short-circuited. The major cause of this type of fault is the heavy wind. The heavy wind swinging the line conductors which may touch together and hence cause short-circuit. The percentage of such types of faults is approximately 15 – 20%.
- Double Line to line Ground Fault (LLG): In double line-to-ground fault, the two lines come in contact with each other along with the ground. The probability of such types of faults is nearly 10 %.
Frequency of occurrence:
- Among the given faults, LG or line to ground fault is most common and occurs frequently.
- The order of frequency of occurrence is given below.
LG > LL > LLG > LLLG
Severity of faults:
- Among the given faults, LLLG or 3 phase faults are most severe. LG or line to ground fault is least severe.
- Line to line fault is more severe than line to ground fault while double line to ground fault is one level severe than LL.
- The order of frequency of occurrence is given below.
LLLG > LLG > LL > LG
Conclusion: Among the given faults, LLLG or 3 phase fault is the most severe and least likely to occur in the power system. LG or line to ground fault is most common one and least severe. The line to line fault is more severe than the line to ground fault while the double line to ground fault is one level severe than LL.
Line To Line To Line Fault Question 10:
A sustained three phase fault occurs in the power system shown in the figure. The current and voltage phasors during the fault (on a common reference), after the natural transients have died down, are also shown. Where is the fault located?
Answer (Detailed Solution Below)
Line To Line To Line Fault Question 10 Detailed Solution
Concept :
As shown in the phasor diagram
- Current I2 & I4 have phase difference of 180°. So that they cancel out each other.
- Magnitude of the current I1 is more than current I3. Also I1 is more lagging than I3
- So that fault is located at point Q.
Line To Line To Line Fault Question 11:
In a large interconnected power system, consider 3 buses having short circuit capacities: 1600 MVA(1) 1200 MVA(2) and 1000 MVA(3) respectively, the voltages of all the buses are 1 pu. If a 3-phase fault takes place on bus 2, the change in bus voltage is described as
Answer (Detailed Solution Below)
Line To Line To Line Fault Question 11 Detailed Solution
When a 3-phase short circuit fault occurs on bus-2, its voltage directly falls to zero i.e., ΔV2 is largest.
Whereas for bus-1 and bus-2, their respective voltages sag due to fault on bus-2.
The more is the short circuit capability of a bus, the less would be the per unit equivalent impedance between the bus and the ground.
Therefore, more will be the strength of the bus i.e., due to fault on other bus, the sag in voltage of a bus would be less, if it has larger/greater short circuit capability.
The correct relation is: ΔV2 > ΔV3 > ΔV1Line To Line To Line Fault Question 12:
A \(50\;MVA,\;10\;kV,\;50\;Hz\), star-connected, unloaded three-phase alternator has a synchronous reactance of 1 p.u. and a sub-transient reactance of \(0.2\;p.u.\) If a 3-phase short circuit occurs close to the generator terminals, the ratio of initial and final values of the sinusoidal component of the short circuit current is ________.
Answer (Detailed Solution Below) 4.9 - 5.1
Line To Line To Line Fault Question 12 Detailed Solution
Fault current is inversely proportional to reactance during fault.
\(\Rightarrow I_f\propto\frac{1}{X}\)
\(\Rightarrow \frac{{intial\;current}}{{final\;current}} = \frac{{Synchronous\;reactance}}{{Sub - transient\;reactance}} = \frac{1}{{0.2}}\) \(= 5\)
Line To Line To Line Fault Question 13:
A generator station having 4 identical generators which are connected to a common bus. The Impedance of each generator is 0.2 pu. A symmetrical fault takes place at the bus bar of the generator.
The sub transient current of the fault is ______ (in pu)Answer (Detailed Solution Below) 20
Line To Line To Line Fault Question 13 Detailed Solution
Z = 0.2 pu
4 parallel identical generators are connected to a common bus and a symmetrical fault occurred at the end of the line.
ER1 = 1.0 pu
As ER1 not given assuming ER1 = 1 pu
\({Z_{eq}} = \frac{Z}{4}\), as 4 identical generators are connected to a common bus
L-L-L fault is occurring at the line end as the fault is a symmetrical fault.
So, the fault current is
\({I_F} = \frac{{{E_{R1}}}}{{{Z_{eq}}}}\)
\( = \frac{{1.0}}{{\frac{{0.2}}{4}}}\)
= 20 p.u
IF = 20 pu
Line To Line To Line Fault Question 14:
A generator is connected to a synchronous motor through a transformer. Reduced to the same base, the pu sub transient reactance’s of the generator and motor are 0.15 pu and 0.35 pu respectively, the leakage reactance of the transformer being 0.1 pu. 3 phase fault occurs at terminals of the motor when the terminal voltage of the generator is 0.9 pu and the output current of the generator is 1 pu at 0.8 pf lag load. Sub transient current fed by the generator in pu is ______
Answer (Detailed Solution Below) 3.7 - 4.2
Line To Line To Line Fault Question 14 Detailed Solution
The terminal voltage of the generator = 0.9 pu
I = 1.0 pu, p.f = 0.8 lag
Equivalent diagram can be drawn as
I = 1.0∠-cos-1 (0.8) = 1.0∠-36.86° = 0.8 - j0.6
Apply KVL,
\( {E_g^{"}} =V_t+ jI_LX_d^{''}\)
EIIg = 0.9 + 0.15 ∠90 × 1.0 ∠-36.86°
= 0.9 + (0.8 + j0.6) × ( j0.15 )
= 0.99 + j0.12
EIIg = (0.99 + j0.12) pu
\({I_g^{"}} = \frac{{{E_g}}}{{j0.15 + j0.1}}\)
\( = \frac{{0.99 + j0.12}}{{j0.25}}\)
= (0.48 - j3.96) pu
Sub-transient current in the generator due to fault is: IIIg = 3.9889 pu
Line To Line To Line Fault Question 15:
The magnitude of three-phase fault currents at buses A and B of a power system are \(10\;pu\) and \(8\;pu\), respectively. Neglect all resistances in the system and consider the pre-fault system to be unloaded. The pre-fault voltage at all buses in the system \(1.0\;pu\) is . The voltage magnitude at bus B during a three-phase fault at bus A is \(0.8\;pu\). The voltage magnitude at bus A during a three-phase fault at bus B, in \(pu\), is ________.
Answer (Detailed Solution Below) 0.83 - 0.85
Line To Line To Line Fault Question 15 Detailed Solution
Voltage at bus B after 3 – phase fault at A \(= 0.8\;p.u.\)
\(\begin{array}{l} {V_B}\; = \;V\left( {prefault} \right)\;-\;{Z_{12}}\; \times \;{I_{f\left( B \right)}}\\ 0.8\; = \;1.0\;-\;{Z_{12}}\; \times \;10\\ {Z_{12}}\; = \;0.02\;p.u.\\ {V_A}\; = \;1.0\;-\;\left( {0.02\; \times \;8} \right)\\ {V_A}\; = \;0.84\;p.u \end{array}\)
Note:
For the voltage magnitude at bus B during a three-phase fault at bus A. So we use fault current of bus A
For the voltage magnitude at bus A during a three-phase fault at bus B. So we use fault current of bus B