In which type of the faults given below, all of the three components Ia0, Ia1 and Ia2 are equal? 

This question was previously asked in
JKSSB JE Electrical 2015 Official Paper
View all JKSSB JE Papers >
  1. Single line to ground fault
  2. Double line to ground fault 
  3. Line to line fault  
  4. 3 phase faults 

Answer (Detailed Solution Below)

Option 1 : Single line to ground fault
Free
JKSSB JE Civil RCC Structures Mock Test
1.2 K Users
20 Questions 20 Marks 20 Mins

Detailed Solution

Download Solution PDF

Explanation:

Fault Analysis in Power Systems

In power systems, faults are abnormal conditions that disrupt the normal flow of electrical current. Fault analysis is crucial to understand the type of fault, its behavior, and its impact on the system. Faults are typically categorized as single line to ground faults, double line to ground faults, line to line faults, and three-phase faults. Each type of fault has unique characteristics that influence the symmetrical components of the system, which are represented by the components Ia0 (zero-sequence current), Ia1 (positive-sequence current), and Ia2 (negative-sequence current).

The question asks us to determine the type of fault in which all three components—Ia0, Ia1, and Ia2—are equal. The correct answer is Option 1: Single line to ground fault. Below is a detailed explanation:

Single Line to Ground Fault:

A single line to ground (SLG) fault is the most common type of fault in power systems and occurs when one phase of the system comes into contact with the ground or a grounded component. This fault can be represented by the following conditions:

  • One phase current becomes significantly larger than the currents in the other two phases.
  • The fault current flows through the ground or the grounded component.
  • The system becomes unbalanced, leading to the presence of zero-sequence, positive-sequence, and negative-sequence components.

In an SLG fault, the following condition holds:

Ia0 = Ia1 = Ia2

This equality occurs because the fault creates a condition where the faulted phase current splits equally among the three symmetrical components. The symmetrical component method is commonly used to analyze unbalanced faults, and for an SLG fault, all three components—zero-sequence, positive-sequence, and negative-sequence currents—are equal in magnitude and phase.

Mathematical Representation:

Assume an SLG fault occurs on phase a. The fault current Ia can be expressed in terms of symmetrical components:

Ia = Ia0 + Ia1 + Ia2

For an SLG fault, the relationship between the symmetrical components is such that:

Ia0 = Ia1 = Ia2

Hence, the faulted phase current Ia becomes:

Ia = 3 × Ia0 (since Ia0 = Ia1 = Ia2)

Meanwhile, the currents in the other two phases (Ib and Ic) remain zero under ideal conditions. This characteristic makes SLG faults unique and relatively straightforward to analyze using symmetrical components.

Impact of SLG Faults:

  • SLG faults are highly unbalanced and can cause significant damage to equipment if not cleared promptly.
  • They are the most frequent type of fault, accounting for approximately 70-80% of all faults in power systems.
  • Protective relays and circuit breakers are designed to detect and clear SLG faults to prevent further damage.

Additional Information

To further understand the analysis, let’s evaluate the other fault types:

Option 2: Double Line to Ground Fault:

A double line to ground (DLG) fault occurs when two phases come into contact with the ground or a grounded component. In this case, the symmetrical components are not equal. The zero-sequence component (Ia0) depends on the grounding impedance, while the positive-sequence (Ia1) and negative-sequence (Ia2) components are influenced by the fault location and the system's impedance. Therefore, Ia0 ≠ Ia1 ≠ Ia2 for a DLG fault.

Option 3: Line to Line Fault:

A line to line (LL) fault occurs when two phases come into contact with each other. In this type of fault, there is no zero-sequence current (Ia0 = 0) because the fault does not involve the ground. The positive-sequence (Ia1) and negative-sequence (Ia2) components are present and are generally not equal. Thus, Ia0 ≠ Ia1 ≠ Ia2 for an LL fault.

Option 4: Three Phase Fault:

A three-phase fault is a balanced fault in which all three phases short-circuit together, either with or without ground involvement. In this case, only the positive-sequence component (Ia1) is present, while the zero-sequence (Ia0) and negative-sequence (Ia2) components are zero. Thus, Ia0 = 0 and Ia2 = 0, and only Ia1 exists, making this fault type entirely different from the SLG fault.

Conclusion:

The correct answer is Option 1: Single line to ground fault, as it is the only fault type where all three symmetrical components—Ia0, Ia1, and Ia2—are equal. Understanding the behavior of symmetrical components for different fault types is essential for fault analysis and the design of protective systems in power networks.

Latest JKSSB JE Updates

Last updated on Jul 1, 2025

-> JKSSB Junior Engineer recruitment exam date 2025 for Civil and Electrical Engineering has been rescheduled on its official website. 

-> JKSSB JE exam will be conducted on 31st August (Civil), and on 24th August 2025 (Electrical).

-> JKSSB JE application form correction facility has been started. Candidates can make corrections in the JKSSB recruitment 2025 form from June 23 to 27. 

-> JKSSB JE recruitment 2025 notification has been released for Civil Engineering. 

-> A total of 508 vacancies has been announced for JKSSB JE Civil Engineering recruitment 2025. 

-> JKSSB JE Online Application form will be activated from 18th May 2025 to 16th June 2025 

-> Candidates who are preparing for the exam can access the JKSSB JE syllabus PDF from official website of JKSSB.

-> The candidates can check the JKSSB JE Previous Year Papers to understand the difficulty level of the exam.

-> Candidates also attempt the JKSSB JE Mock Test which gives you an experience of the actual exam.

More Fault Analysis Questions

Get Free Access Now
Hot Links: teen patti download apk teen patti gold apk download teen patti 100 bonus lucky teen patti teen patti master downloadable content