Question
Download Solution PDFSymmetrical components are used in power system for the analysis of
Answer (Detailed Solution Below)
Detailed Solution
Download Solution PDFSymmetrical components:
Any unbalanced system of n phasors can be resolved into the n-system of balanced phasors. These subsystems of balanced phasors are called symmetrical components. These are used in the analysis of unbalanced three-phase faults.
Positive sequence components:
Set of three phasors equal in magnitude, displaced from each other by 120° in phase, and having the same phase sequence as the original phasors constitute positive sequence components. They are denoted by suffix 1.
Negative sequence components:
Set of three phasors equal in magnitude, displaced from each other by 120° in phase, and having phase sequence opposite to that original phasors constitute the negative sequence component. They are denoted by suffix 2.
Zero sequence components:
The set of three phasors equal in magnitude and all phases (with no mutual phase displacement) constitute zero sequence components. They are denoted by suffix 0.
Last updated on Jul 2, 2025
-> ESE Mains 2025 exam date has been released. As per the schedule, UPSC IES Mains exam 2025 will be conducted on August 10.
-> UPSC ESE result 2025 has been released. Candidates can download the ESE prelims result PDF from here.
-> UPSC ESE admit card 2025 for the prelims exam has been released.
-> The UPSC IES Prelims 2025 will be held on 8th June 2025.
-> The selection process includes a Prelims and a Mains Examination, followed by a Personality Test/Interview.
-> Candidates should attempt the UPSC IES mock tests to increase their efficiency. The UPSC IES previous year papers can be downloaded here.